Over the plant room door there's a hole in the blockwork where an old cable came out, and nobody filled it.
On a compartment wall, that needs sealing with a tested product.
protestesltd.co.uk/fire-stop…
11
Cleaning cage clipped the bottom corner of the kitchen corridor fire door back in September, and the facing has peeled a little further every week since. 🧹
1
14
We'd make that call door by door and write the reason down either way, so it's on file when an auditor or assessor asks why.
1
2
How we work through repair or replace across a site: protestesltd.co.uk/fire-door…
4
Strips, smoke seals or both? The door's test evidence sets the strips and its position sets the smoke seals, so FD30S stair doors need both. protestesltd.co.uk/fire-door…
32
New hardware on an old fire door is worth a second look 🔩
- handles bolted through in new spots
- hinges from a general hardware store
- empty screw holes
It's all part of the tested door.
🌐 protestesltd.co.uk?utm_sourc…
📞 01604 696113
8
Unhooking the closer arm leaves the closer bolted to the door looking normal, while the door stays wherever it was last left. 🚪
On a corridor that's busy all day, the closer is what gets that door shut after every person through it. 🔧
9
Above the ceiling tiles, the corridor wall stops just short of the slab, leaving an open strip along the top of the blockwork.
That joint needs fire stopping too.
protestesltd.co.uk/passive-f…
17
Back in October the stair door by the loading bay started sticking after a wet week, so someone took a plane to the latch edge and it shut nicely again. 🪵
1
2
223
The better route is to find the moisture, let the door settle and then reassess it. A badly swollen or delaminated leaf is usually a replacement, and trimming it rarely saves it.
1
2
Before anyone picks up a plane, check the door's label or plug and its evidence for how much can come off.
How we put doors like this right: protestesltd.co.uk/fire-door…
2
Coat hooks screwed into the back of a meeting room fire door are easy to miss. 🧥 Two more:
- noticeboards fixed through the leaf
- bolts added for privacy
Each one changes a tested door.
🌐 protestesltd.co.uk?utm_sourc…
📞 01604 696113
1
19
Cracked glass in a fire door vision panel matters because the glass, beads and glazing seal were all part of what the door was tested with. 🪟
The replacement has to match that evidence too. When did anyone last check yours? 🔍
2
26
Riser access panel leaning against the corridor wall, and the opening behind it left wide open into the riser.
If the riser wall is fire-resisting, that panel is part of it.
protestesltd.co.uk/fire-comp…
17
A slamming fire door usually needs its closer adjusted in small turns, then testing from every angle so it still latches. protestesltd.co.uk/fire-door…
Somebody swapped the lock on the plant room fire door a while back, and the old cut-out is still there under a smear of wood filler and a coat of paint. 🔩
1
24
Small redundant screw holes can often be made good with a method the manufacturer allows. A bigger cut-out needs a proper look, and sometimes it's the reason the leaf has to be replaced.
1
3
We check old hardware holes on every door and either repair them to the evidence or tell you plainly that the leaf needs replacing: protestesltd.co.uk/fire-door…
4